Permit: T09CM02185

Parcel: 136080510


Addresses:

2002 S FAYE PL

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/09/2010 ELECTRIC - FINAL Approved IVRS - Inspection :*
01/21/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
01/14/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) UNDERGROUND METAL CONDUIT NEEDS TO BE PRIMED AND TAPED
2) EAST BLDG SUB PANEL NEEDS IT'S OWN GROUNDING SYSTEM-2 DRIVEN RODS 8' DEEP AND 6' APART
09/10/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED TO SEE UNDERGROUND CONDUIT
2) NEED GFI PROTECTION IN BOTH SHEDS