Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/09/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 01/21/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 01/14/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) UNDERGROUND METAL CONDUIT NEEDS TO BE PRIMED AND TAPED 2) EAST BLDG SUB PANEL NEEDS IT'S OWN GROUNDING SYSTEM-2 DRIVEN RODS 8' DEEP AND 6' APART |
|
| 09/10/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED TO SEE UNDERGROUND CONDUIT 2) NEED GFI PROTECTION IN BOTH SHEDS |