Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/30/2009 | ELECTRIC - RECONNECT | Approved | ||
| 09/24/2009 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) POST UNIT NUMBERS VISIBLE FROM STREET 2) HAZARDOUS ELECTRICAL EXTERIOR JUNCTION NOT ATTACHED. ROMEX INSULATION NOT IN BOX 3) MIXED BREAKER TYPES IN PANEL 4) SEAL KNOCKOUT PANELS 5) ADDED CIRCUITS TO COOLER CONDUIT NOT SECURED NOT CONNECTED TO BREAKERS 6) UNITS HAVE BEEN REWIRED. MISSING HARD WIRED SMOKE DETECTORS 7) MISSING OUTLETS PER CODE 8) MISSING SWITCHED FIXTURES TO ALL EXIT DOORS 9) PROVIDE ACCRESS TO ROOF |
|
| 09/09/2009 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 08/21/2009 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) APARTMENTS REMODELED AND NO PERMITS ON FILE 2) EXPOSE ALL OUTLETS AND SWITCHES AND REMOVE COVERS AT ELECTRIC SERVICE PANELS 3) PERMITS REQUIRED FOR NEW WATER HEATER 4) GAS LINE NOT HOLDING PRESSURE 5) SMOKE ALARMS REQUIRED IN BEDROOMS AND HALL 5) FILL IN BLANKS AT ELECTRIC PANELS 6) HAVE LICENSED ELECTRICIAN CHECK ALL ELECTRICAL FOR CODE COMPLIANCE NEED RESULTS IN WRITING ON HIS COMPANY LETTER HEAD 6) OUTLETS IN BATHROOM AND KITCHEN SHALL BE GFI PROTECTED 7) LICENSED ELECTRICIAN TO VERIFY THAT APTS WERE NOT RECENTLY REWIRED |