Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/09/2010 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 06/08/2010 | BUILDING - FINAL | Partial Approval | IVRS - Inspection :* 1) ALL OK PENDING CERTS |
|
| 06/07/2010 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) ITEMS NOT CORRECTED |
|
| 06/03/2010 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) LABEL SERVICE FOR NON H20 BONDED SYSTEM 2) 60/60 BREAKER ON #8 CU. ROMEX ? OPEN 3) NEED NO LUX ON ALL AL. CONDUCTOR CONNECTIONS 4) NORTH A/C UNIT MAX 35/35-40/40 INSTALLED 5) MAX FUSE IN SO. UNIT CANNOT READ LABEL 6) NEED ANTI SIPHON AT ALL HOSE BIBS 7) CLEANOUT CAP FRONT MAIN 8) NEED RECEPT COVER DISPOSAL 9) CLEANOUT COVER KIT SINK 10) RECEPT UNDER KIT. COUNTER NOT ALLOWED USE BLANK COVER 11) LOOSE WALL RECEPT S. BEDROOM NEXT TO DOOR 12) NEED OVERFLOW PROTECTION CONDENSATE PAN A/C 2ND FLOOR 13) BOND GRD. BUSS TO CABINET SUB-PANEL 2ND FLOOR |