Permit: T09CM02154

Parcel: 129020470


Addresses:

2916 E BROADWAY BL

Inspection Status: Approved

Inspection History: MECHANICAL - HOODS

Date Description Inspector Results Comments
02/23/2010 MECHANICAL - HOODS Approved
02/04/2010 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
02/02/2010 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
1) DUCT FIRE WRAP OK
2) HOOD HUNG OK
3) ROOF JACK AT GREASE DUCT OK
01/29/2010 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
1) GREASE DUCT SMOKE TEST OK
2) 2 LAYERS FIRE WRAP OK THRU ROOF
01/28/2010 MECHANICAL - HOODS Not ready for Inspection IVRS - Inspection :*
1) GREASE DUCT LEAK TEST FAILED