Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T09CM02145
Inspection Description - FRAMING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/09/2009 | FRAMING | Approved | ||
| 10/13/2009 | FRAMING | Partial Approval | IVRS - Inspection :* 1) DAMAGED WEB ON TRUSS REPLACED, NEED REPAIR DETAIL FOR OUR RECORDS DEPT. |
|
| 10/08/2009 | FRAMING | Partial Approval | IVRS - Inspection :* 1) A01 TRUSS DAMAGE |
|
| 10/07/2009 | FRAMING | Partial Approval | IVRS - Inspection :* 1) OK TO INSULATE 2) GARAGE TO HOUSE SHEARWALL, TWO H.D.'S SOUTH OF MAN DOOR, OSB TO BE NAILED TO STUDS ATTACHED TO H.D. |
|
| 10/06/2009 | FRAMING | Not ready for Inspection | IVRS - Inspection :* 1) FROM LAST INSPECTION ITEMS NOT DONE 1,2,3 & 6 |
|
| 10/05/2009 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) DRYWALL BACKING HALL TUB AND MASTER 2) SECURE WALL TOP PLATE HALL BATH TO BEDROOM 3) TRUSS WEB CUT 4TH TRUSS FROM REAR WALL, MARKED ON FLOOR BELOW, SAW KERF IN WEB 4) BLOCK MECH DUCT MSTR TOILET 5) SHEARWALL ADD STUD NEXT TO DRYER BOX 6) INTERIOR SHEARWALLS, NAIL ALL STUDS TO OSB AT H.D.'S |