Permit: T09CM02139

Parcel: 135021830


Addresses:

6434 E CALLE BOOTIS

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
02/26/2010 BUILDING - FINAL Approved IVRS - Inspection :*
02/23/2010 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SHOWER LIGHT MUST BE A WATERPROOF FIXTURE WITH COVER
2) FURNACE GAS LINE NEEDS DRIP LEG PRIOR TO UNIT
3) REMOVE HORIZONTAL TPR DRAIN PIPE
4) ROMEX BEHIND FRIDGE NEEDS TO BE IN CONDUIT
5) LABEL BREAKERS
6) DBL TAPED WIRES MUST BE OF SAME SIZE
7) PAINT ROOF ABS