Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/02/2009 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 09/29/2009 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GFCI PROTECT KITCHEN OUTLETS CIRCUIT A1 PER PLAN 2) A5 AND A6 OUTLETS TEST OPEN GROUND IN BEDROOMS 2 WIRE OUTLETS SWITCHED TO OUTLETS WITH GROUND. RESTORE TO 2 WIRE OR GFCI ? OF EACH CIRCUIT 3) PROTECT NM CABLE IN STORAGE ROOM FROM PHYSICAL DAMAGE UNDER 8' 4) VERIFY GROUND RODS LOCATION MAIN SERVICE PANEL 5) EXPOSED WIRING DINING ROOM FIXTURE |