Permit: T09CM02125

Parcel: 12620001C


Addresses:

1030 S RANDOLPH WY


Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T09CM02125

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
03/01/2010 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
01/28/2010 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) FINISH VDV
01/27/2010 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) CORDS NOT ALLOWED ABOVE CEILING 400.7 & 8
2) SUPPORT VDV CABLING 725.24 AND 300.11
3) OK TO TILE SUBJECT TO OTHERS EXCEPT AS NOTED