Permit: T09CM02121

Parcel: 110140170

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T09CM02121

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/05/2010 MECHANICAL - FINAL Approved IVRS - Inspection :*
01/28/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CONDENSATE DRAIN RUNS UP HILL TO THE ROOF PENETRATION
2) 3/8" ID X 18" GAS FLEX NOT ADEQUATE FOR 100,000 BTU FURNACE
3) A/C UNIT IS OVERFUSED
4) EXTEND WATER HEATER VENT MINIMUM 3' ABOVE COMBUSTION AIR INTAKE
5) BE SURE TO USE DBL WALL AMERIVENT PIPE
6) REMOVE THE SCREEN FROM DRYER VENT T-TOP ALSO REMOVE LINT