Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/05/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 01/28/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CONDENSATE DRAIN RUNS UP HILL TO THE ROOF PENETRATION 2) 3/8" ID X 18" GAS FLEX NOT ADEQUATE FOR 100,000 BTU FURNACE 3) A/C UNIT IS OVERFUSED 4) EXTEND WATER HEATER VENT MINIMUM 3' ABOVE COMBUSTION AIR INTAKE 5) BE SURE TO USE DBL WALL AMERIVENT PIPE 6) REMOVE THE SCREEN FROM DRYER VENT T-TOP ALSO REMOVE LINT |