Permit: T09CM02112

Parcel: 132161260


Addresses:

4821 S CALLE OLE

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
10/15/2009 BUILDING - FINAL Approved IVRS - Inspection :*
1) ALL CORRECTIONS COMPLETED
10/01/2009 BUILDING - FINAL Partial Approval IVRS - Inspection :*
1) USE APPROVED TERMINATION FOR GROUNDS IN JUNCTION BOX
2) TIGHTEN LOOSE LEG SUPPORTS
3) SECURE LOOSE CABLE UP UNDER MODULES
4) LABEL BREAKERS 408.4 AND 490.17
5) TIGHTEN LOOSE FITTINGS AND SUPPORT RACEWAYS
6) VERIFY CONDUCTOR FILL FOR RACEWAYS
7) FILL UNUSED OPENING IN PANEL
8) MAINTAIN WORKING CLEARANCES 110.26
9) USE APPROVED MOUNTING HARDWARE NOT DRYWALL SCREWS
10) VERIFY 25 OHMS-GROUND RODS