Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/23/2009 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 11/20/2009 | MECHANICAL - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 09/17/2009 | MECHANICAL - INTERMEDIATE | Not ready for Inspection | 1. PROVIDE SECONDARY DRAIN ON ALL UNITS. 2. CONDENSATE PUMP LEAKING 3. INSULATION ON LINE SETS IN ATTIC TURN AND CONDENSING IN ATTIC SPACE 4. FLUE PIPING INSTALLED INCORRECTLY 5. PROVIDE 6" CLEARENCE TO COMBUSTIBLES FROM FLUE PIPING 6. PROVIDE SEDIMENT TRAPS ON GAS PIPE 7 FLEX PIPING NOT ALLOWED ON T & P * NOTE ARRESSES ARE NOT CORRECT IN REFERENCE TO BUILDINGS. CORRECT PRIOR TO NEXT INSPECTIONS C.O.T. |
|
| 09/16/2009 | MECHANICAL - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* |