Permit: T09CM02101

Parcel: 133384150

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
09/22/2009 BUILDING - FINAL Approved IVRS - Inspection :*
09/17/2009 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
2:35 PM NO ACCESS FOR INSPECTION
08/31/2009 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*
1) SEE ALL NOTES FROM 8/11/09 AND COMPLY
2) PLASTIC SUPPORTS FOR ALL PIPING TO ROOF AND PROPERLY SECURE PIPING TO SUPPORTS
3) PROVIDE CORRECT COLOR WIRES FOR CIRCUIT
4) PROVIDE CORRECT APPROVED HANDLE TIE FOR BREAKER OR PROVIDE CORRECT BREAKER
5) PRESSURE RELIEF ON COLD SIDE TO TERMINATE MAXIMUM OF 24
FROM FINISH GRADE
08/11/2009 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*
1) ALL PIPING ON ROOF TO BE SUPPORTED UP OFF OF ROOF
2) PROVIDE BACK UP NUT ON WIRING CONNECTOR TO HEATER ON ROOF. TIGHTEN ALL CONDUIT CONNECTIONS
3) PROVIDE ROOF JACK FOR ELECTRICAL CONDUIT THRU ROOF
4) PROVIDE PRESSURE RELIEF ON COLD WATER INLET PER PLAN
5) PROVIDE CIRCUIT BREAKER LABELED FOR ELECTRIC WATER HEATER WITH CORRECT WIRE SIZE PER PLAN