Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T09CM02095

Parcel: 140420200


Addresses:

2801 E ELVIRA RD


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T09CM02095

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/30/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
1) OK ELECTRIC
11/25/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
11/13/2009 ELECTRIC - FINAL Partial Approval OK FOR TCO PER RHOLLAND
11/13/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) OK ITEMS FROM LAST INSPECTION
11/12/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) BOXES MORE THAN 1/4" 314.20
2) EXCESS PAINT ON DEVICE TERMINALS
3) NEED DISCONNECTING MEANS FOR INSTA HOT
4) FINISH PANEL DIRECTORIES 408.4
5) PLEASE VERIFY COMMON TRIP DEVICES
6) BOND AT CONCENTRICS OVER 250V 250.97
8) FINISH LABELING
9) FILL UNUSED OPENINGS IN PANELS
10) BOND FLEX RACEWAY FOR XFMR
11) VERIFY VOLTAGE OF CABLE IN LIGHTING CONTROLS