Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/30/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) OK ELECTRIC |
|
11/25/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
11/13/2009 | ELECTRIC - FINAL | Partial Approval | OK FOR TCO PER RHOLLAND | |
11/13/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) OK ITEMS FROM LAST INSPECTION |
|
11/12/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) BOXES MORE THAN 1/4" 314.20 2) EXCESS PAINT ON DEVICE TERMINALS 3) NEED DISCONNECTING MEANS FOR INSTA HOT 4) FINISH PANEL DIRECTORIES 408.4 5) PLEASE VERIFY COMMON TRIP DEVICES 6) BOND AT CONCENTRICS OVER 250V 250.97 8) FINISH LABELING 9) FILL UNUSED OPENINGS IN PANELS 10) BOND FLEX RACEWAY FOR XFMR 11) VERIFY VOLTAGE OF CABLE IN LIGHTING CONTROLS |