Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T09CM02095
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/30/2009 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
11/25/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
11/16/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* COMM ROOM: 1) IS EMT LISTED 2) BOND CABLE TRAYS 3) VDV LAYING ON GRID |
|
10/23/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
10/21/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :*EAST SIDE OF MAIN FLOOR POWER POLES, 118, LUBY, 117, 116, 115, 114, CEILING OK IT BATTERY BACKUP SYSTEM UPS PLATFORM OK |
|
10/16/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
10/15/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
10/13/2009 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1) CONTRACTOR CANCELLED |
|
10/09/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
10/08/2009 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
10/06/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK COLUMNS 7 TO 9 OPEN ROOM 2) ELECTRIC ABOVE CEILING 3) EXCEPT POWER POLES |
|
10/02/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) VDV CABLING 725.24 AND 300.11 2) OK ROOM 105 ELECTRIC ABOVE CEILING |
|
10/01/2009 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
09/11/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* |