Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T09CM02095
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/30/2009 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
11/25/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) EMT TO BE LISTED 362.6 2) CABLE TRAY BONDING PER 392.6 |
|
11/06/2009 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) CLEAR POWER FOR TMPP |
|
11/05/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) BOND METAL RACEWAY 2ND SWITCHBOARD 2) NEED LETTER OF TORQUE 3) NEED LABEL PER 702.8 4) FILL UNUSED OPENING TRANSFER SWITCH 5) USE CORRECT SIZED LUG FOR CONDUCTORS |
|
10/23/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK EM LIGHTS RESTROOMS 2. OK MAKUP TO POWER POLES WEST END OF SPACE |
|
10/16/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK FURNITURE CONNECTIONS AT WALL LOCATIONS 2) OK CEILING ROOMS 104, 103 & 102 |
|
10/15/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK CEILINGS WEST END OF OPEN AREA WITH EXCEPTION OF CONNECTIONS TO POWER POLES 2) ON PLANS GENERATOR AND SERVICE SHOW AS FUTURE |
|
10/09/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK COLUMN 7 TO EAST BATHROOM WALL 2) OK BATHROOM HARD LIDS-CHECK EM CANS LATER |
|
10/01/2009 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) VDV CABLING TO BE SUPPORTED 725.24, 800.24, 300.11 AND 392.6 |
|
09/11/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK WALLS 109 AND 110 2) OK HARD LID ROOM 112 |
|
09/03/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK WALLS 105 AFTER TIGHTING LOOSE FITTINGS |