Permit: T09CM02095

Parcel: 140420200


Addresses:

2801 E ELVIRA RD


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T09CM02095

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
11/30/2009 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
11/25/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) EMT TO BE LISTED 362.6
2) CABLE TRAY BONDING PER 392.6
11/06/2009 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) CLEAR POWER FOR TMPP
11/05/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) BOND METAL RACEWAY 2ND SWITCHBOARD
2) NEED LETTER OF TORQUE
3) NEED LABEL PER 702.8
4) FILL UNUSED OPENING TRANSFER SWITCH
5) USE CORRECT SIZED LUG FOR CONDUCTORS
10/23/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK EM LIGHTS RESTROOMS
2. OK MAKUP TO POWER POLES WEST END OF SPACE
10/16/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK FURNITURE CONNECTIONS AT WALL LOCATIONS
2) OK CEILING ROOMS 104, 103 & 102
10/15/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK CEILINGS WEST END OF OPEN AREA WITH EXCEPTION OF CONNECTIONS TO POWER POLES
2) ON PLANS GENERATOR AND SERVICE SHOW AS FUTURE
10/09/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK COLUMN 7 TO EAST BATHROOM WALL
2) OK BATHROOM HARD LIDS-CHECK EM CANS LATER
10/01/2009 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) VDV CABLING TO BE SUPPORTED 725.24, 800.24, 300.11 AND 392.6
09/11/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK WALLS 109 AND 110
2) OK HARD LID ROOM 112
09/03/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK WALLS 105 AFTER TIGHTING LOOSE FITTINGS