Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CONSTRUCTION POWER
Permit Number - T09CM02094
Inspection Description - ELECTRIC - CONSTRUCTION POWER
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/13/2009 | ELECTRIC - CONSTRUCTION POWER | Approved | IVRS - Inspection :* | |
08/12/2009 | ELECTRIC - CONSTRUCTION POWER | Partial Approval | IVRS - Inspection :* 1) NEED MANUFACTURES HOLDOWN ON MAIN 2) FILL UNUSED OPENING 3) TIGHTEN LOOSE FITTINGS |
|
08/11/2009 | ELECTRIC - CONSTRUCTION POWER | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* TRAILER: 1) NEED GROUNDING ELECTRODE SYSTEM 2) NEED MAIN BREAKER 3) PROTECT CONDUCTORS FORM SHARP METAL EDGES IN BACK OF JUNCTION BOX 4) PLEASE PROVIDE FLEXABILITY TO TRAILER 5) REMOVE BOND SCREW 6) INSTALL CONDUCTORS IN FULL RACEWAY SYSTEM INSIDE PANEL: 1) FILL UNUSED OPENING 2) LABEL BREAKERS 3) ONLY ONE CONDUCTOR TO LUG 4) CANNOT USE SHEET METAL THREAD SCREWS AND CLEAN SURFACE UNDER LUG |