Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
04/08/2010 FRAMING Approved
04/06/2010 FRAMING Not ready for Inspection IVRS - Inspection :*
CANCELED BY WALTER
03/29/2010 FRAMING Not ready for Inspection IVRS - Inspection :*
1) NEED LADDER TO ROOF
2) BOTH UNITS NEED WATER HAMMER PROTECTION AT WASHER BOX AND DISHWASHER
3) BLANK OFF RECEPT, UNDER KIT. COUNTER OVERHANG OF INSTALL A FACELESS GFCI
4) SEE NOTES ABOUT FRAMING INSPECTION, NEXT LOT
01/11/2010 FRAMING Partial Approval IVRS - Inspection :*
1) ROMEX TO EXHAUST FAN POWDER ROOM (NOT CONNECTED)
2) DROP CEILING KIT. NOT SECURED
3) CANNOT FIND ON PLAN NAIL SCHEDULE FOR SHEAR AND NOT SHEARWALL BOTTOM PLATES
4) VERT BACKING AT MSTR. SHOWER FOR DRYWALL CORNER NAILING
01/05/2010 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) GARAGE EXTERIOR LIGHTS NOT INSTALLED
2) NAIL OFF STAIR STRINGER A-35 CLIPS
3) SHIM UNDER STEP FRAME BETWEEN 2 PLATFORMS
4) RELOCATE OUTLETS ON FURRED N. GREAT ROOM WALL
5) RE-SUBMIT UTILITY ROOM CHANGES ON PLAN
6) RE-FRAME WHERE UTILITY ROOM 3" ABS IS OUT OF WALL
7) FHA STRAP TOP PLATE OVERBORDE FOR WIRES-N.E. OF TOP OF STAIRS-NOT BANG PLATES
8) NO INSULATION BEHIND TUB AND SHOWER SURROUNDS
9) RE-NAIL SHINERS IN HALL BATH SOUTH WALL OSB
10) NEED DWV AND H20 PRESSURE