Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/28/2009 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* 1) OK CEILING TILES |
|
| 10/26/2009 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection 1) DUCT JOINTS NOT SEALED 2) INSULATE CANS AT REGISTERS* |
|
| 10/15/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) SUPPLY AND RETURN DIFFUSERS DO NOT HAVE LINED BOXES OVER THEM 2) PROVIDE A LETTER FROM ENGINEER TO DELETE ANYTHING FROM PLANS 3) OK FOR CEILING TILES OPEN OFFICE #110 |
|
| 09/01/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK FOR HARD LIDS |