Permit: T09CM02063

Parcel: 10818716A

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T09CM02063

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
10/28/2009 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
1) OK CEILING TILES
10/26/2009 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection
1) DUCT JOINTS NOT SEALED
2) INSULATE CANS AT REGISTERS*
10/15/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) SUPPLY AND RETURN DIFFUSERS DO NOT HAVE LINED BOXES OVER THEM
2) PROVIDE A LETTER FROM ENGINEER TO DELETE ANYTHING FROM PLANS
3) OK FOR CEILING TILES OPEN OFFICE #110
09/01/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) OK FOR HARD LIDS