Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: ELECTRIC - SERVICE UPGRADE
Permit Number - T09CM02062
Inspection Description - ELECTRIC - SERVICE UPGRADE
Inspection Status - Not ready for Inspection
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/16/2009 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* | |
09/16/2009 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
09/09/2009 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* CANCELLED BY CONTRACTOR |
|
09/04/2009 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) 30 AMP CIRCUIT REQUIRE #10 GROUND. SEE PLANS AND NEC 250.122 2) INSTALL PROTECTIVE BUSHING ON FEEDER CONDUCTORS TO PANEL 3) INSTALL ALL MOUNTING HARDWARE FOR RECEPTACLES MOUNTED IN INDUSTRIAL COVERS 4) CONNECT EQUIPMENT GROUNDS TO METAL BOXES 5) STRAP MC CABLE WITHIN 12" OF CONNECTIONS 6) CANNOT USE EMT AS CABLE OR PIPE SUPPORT 7) OPEN LIGHT FIXTURES FOR INSPECTION. ENSURE DISCONNECTING MEANS PER NEC 410.73 8) BREAKERS IN PANEL TO BE RATED 22 KAIL SEE NOTE #1 9) INSTALL BONDING JUMPER TO METER ENCLOSURE FROM GROUNDED CONDUCTOR 10) EXPLAIN EQUIPMENT GROUND WITH SERVICE CONDUCTORS 11) INSTALL REJECTION PINS AT SERVICE DISCONNECT 12) OPEN GUTTER FOR INSPECTION |