Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
09/22/2009 MECHANICAL - FINAL Approved IVRS - Inspection :*
1) CORRECTIONS HAVE BEEN MADE
09/17/2009 MECHANICAL - FINAL Partial Approval WIRE SPLICES ON HIGH VOLTAGE MUST BE DONE IN AN APPROVED J BOX FOR ALL MINI SPLIT FOR COILS.
09/16/2009 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
09/01/2009 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE MINIMUM 15A DISCONNECT SWITCH AT EACH FAN COIL
2) PROVIDE A HOSE CLAMP ON BARBED FITTING
3) CONNECT OVERFLOW SENSORS
4) SECURE THE DRAIN HOSE CONNECTIONS FROM FAN COIL INTO PUMPS-ALL FUJITSU UNITS
5) USE AN APPROVED EQUIPMENT CORD AT RHEEM FAN COIL
6) SECURE THE VENT CONNECTOR
7) PROVIDE PURPLE PRIMER ON ALL PVC FITTINGS PRIOR TO GLUE
8) ELECTRIC ON ROOF OK