Inspection History Details
Inspection Status: Denied
Inspection History: FRAMING
Permit Number - T09CM02050
Inspection Description - FRAMING
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/19/2011 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CONSULT WITH QUALIFIED ELECTRICIAN 2) ALL ROMEX TERMINATED INTO APPROVED BOX. SERVICE ROMEX 8" FROM BOXES THROUGHOUT 3) INSTALL RANGE CIRCUIT 4) 2-20 AMP GFCI SMALL APPLIANCE CIRCUITS KITCHEN 12-2 WIRE 5) ISOLATE REFRIDGERATOR CIRCUIT 20 AMP 6) MAKE UP ALL SWITCHES PIG TAIL GROUNDS 7) MISSING CIRCUIT 2 SMOKE ALARM CIRCUIT 14-3 WIRING 8) MISSING CIRCUITS 12, 13, 14 & 15 BASE BOARD HEATERS 12-2 WIRING 9) PROVIDE SWITCHED LIGHT FIXTURES EXIT DOORS 10) MISSING BATH 20 AMP 12-2 OUTLET. TERMINATE EXHAUST FAN WIRING INTO BOX 11) TERMINATE HOMERUNS INTO PANEL 12) BEDROOM WINDOWS SILL HEIGHT ABOVE 44" MINIMUM OPENING SIZE 20" X 24"-20" WIDTH 13) FIREBLOCK DROPPED CEILINGS 14) STOPPED INSPECTION |
|
09/27/2011 | FRAMING | Not ready for Inspection | IVRS - Inspection :* 1) GATE LOCKED AND NO ACCESS |
|
06/09/2010 | FRAMING | Not ready for Inspection | IVRS - Inspection :* |