Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/16/2009 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 12/10/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) PLAN NOT STAMPED BY ELECTRICAL PLANS EXAM 2) VERIFY THERMAL PROTECTION ON MOTORS PER NOTE: #1 ON ELECTRICAL NOTES |
|
| 12/09/2009 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) COMPRESSOR DISCONNECT NEEDS GROUNDING REDONE, K.O. SEALS NEED BLANKS ON PANEL 2) NEED GROUNDING SYSTEM FROM PANEL TO BLOWER DISCONNECTS 3) NEED STRAPPING ON DISCONNECTS TO BOOTHS 4) NEED BOX ON NORTH OF PANEL BLANKED OFF |