Permit: T09CM02042

Parcel: 129111660

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
06/25/2010 BUILDING - FINAL Approved CERTS TURNED IN
05/12/2010 BUILDING - FINAL Partial Approval IVRS - Inspection :*
1) NEED STUCCO AND INSULATION CERTS
05/11/2010 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) LIGHTS, FANS AND SMOKE ALARM SHALL BE ARC FAULT PROTECTED
2) CONDENSATION LINE SHALL HAVE 1/4" PER FOOT SLOPE AND SECURE TO ROOF AT 48" ON CENTER
3) COMPLETE WATER HEATER APPEAL PAPERWORK
4) 21" CLEARANCE REQUIRED IN FRONT OF WATER CLOSET
05/07/2010 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PAINT ROOF VENTS ABS
2) LOWER CLEANOUTS TO GRADE
3) VACUUM BREAKER HOSE BIB
4) OVERHANG AT BATHROOM OVER FENCE LINE. FIRE RATED ? WHERE IS PROPERTY LINE ?
5) COMPLETE GRADING SLOPE AWAY FROM BLDG
6) COMPLETE CONDENSATE LINE TO ROOFS EDGE
7) COPPER OR CVPC TPR WATER HEATER. TPR LINE MUST SLOPE DOWNWARD ANGLE OUT-APPEAL REQUIRED
8) GFCI PROTECT OUTLET LIVING ROOM SINK
9) ARC FAULT BEDROOM OUTLETS
10) RELOCATE BATH GFCI OUTLETS PER CODE