Permit: T09CM02035

Parcel: 137116010


Addresses:

1522 W DELAHUNT ST

Inspection Status: Approved

Inspection History: EXCAVATION/LAYOUT REBAR & ZON

Date Description Inspector Results Comments
08/14/2009 EXCAVATION/LAYOUT REBAR & ZON Approved IVRS - Inspection :*
08/13/2009 EXCAVATION/LAYOUT REBAR & ZON Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE PROPER DEPTH SOIL MINIMUM 3 1/2". NEW PORCH REQUIRES 2" MINIMUM FROM WEEP
2) EXPANSION JOINT REQUIRED AT EXISTING
3) COMPACT SOIL 95 PERCENT
4) PROVIDE 8" TOE ALL EDGES
5) REMOVE #3 BARS IN FOOTERS TO #4 2 EACH WAY PER DETAIL 3/2
08/12/2009 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
1) PORCH SLAB TO BE POURED LATER. 2" FROM STUCCO STOP TO SLAB
2) OK PER LEE RAY TO POUR AGAINST STUCCO