Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/07/2010 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 11/15/2010 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 11/09/2010 | MECHANICAL - ABOVE CEILING | Partial Approval | ||
| 11/08/2010 | MECHANICAL - ABOVE CEILING | Partial Approval | ||
| 10/13/2010 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) CLEARANCE AT F.D.'S THRU WEST WALL OK 2) DO NOT CUT OR ALTER FIRE DAMPERS. REPLACE ANY DAMPERS ALTERED 3) EAST MECH ROOM DAMPERS TO SHORT FOR 12" WALL-CLEARANCE OK |
|
| 10/07/2010 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 10/06/2010 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) ALL FIRE DAMPERS ARE TO BE INSTALLED PER MANUFACTURES INSTALLATION INSTRUCTIONS. DO NOT ALTER INSTALLATION IN ANY WAY 2) PROVIDE ALL CLEARANCES AND GAPS, ANGLES, ECT... AS CALLED OUT IN INSTALLATION INSTRUCTIONS 3) PROVIDE MANUFACTURES INSTALLATION INSTRUCTIONS FOR NEXT INSPECTION |