Permit: T09CM02029

Parcel: 14016003B


Addresses:

5085 S CHERRY AV


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T09CM02029

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
12/03/2010 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
10/12/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK ROOM 111 LID AND WALLS
10/01/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) NO MORE THAN 360 DEGREE IN CONDUIT RUNS
2) PROTECT VDV CABLING FROM SHARP METAL EDGES
3) IDENTIFY FIRE ALARM BOXES PER 760
4) FINISH ROOM 111
09/24/2010 ELECTRIC - INTERMEDIATE Partial Approval 1) OK STUD FRAMED WALLS
09/23/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
09/22/2010 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) CANCELLED
09/21/2010 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) PROTECT PVC AT BASE PLATES
2) MISSING PLASTER RINGS
3) SUPPORT CONDUIT AND M/C CABLES PER CODE
4) TIGHTEN LOOSE FITTINGS
5) PREVENT DIELECTRIC CONTACT
6) PROTECT M/C CABLE AT SHALLOW STUDS
09/20/2010 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) CANCELLED