Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T09CM02029
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/03/2010 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
10/12/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK ROOM 111 LID AND WALLS |
|
10/01/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) NO MORE THAN 360 DEGREE IN CONDUIT RUNS 2) PROTECT VDV CABLING FROM SHARP METAL EDGES 3) IDENTIFY FIRE ALARM BOXES PER 760 4) FINISH ROOM 111 |
|
09/24/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | 1) OK STUD FRAMED WALLS | |
09/23/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
09/22/2010 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED |
|
09/21/2010 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) PROTECT PVC AT BASE PLATES 2) MISSING PLASTER RINGS 3) SUPPORT CONDUIT AND M/C CABLES PER CODE 4) TIGHTEN LOOSE FITTINGS 5) PREVENT DIELECTRIC CONTACT 6) PROTECT M/C CABLE AT SHALLOW STUDS |
|
09/20/2010 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED |