Permit: T09CM01992

Parcel: 125101180


Addresses:

3725 E 2ND ST #D

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
07/29/2009 PLUMBING - FINAL Approved IVRS - Inspection :*
07/28/2009 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) TEMPERATURE AND PRESSURE RELIEF DRAIN PIPING SHALL GRAVITY DRAIN TO DAYLIGHT AND BE OF APPROVED DRAINAGE MATERIAL (NO FLEX)
2) THIS DRAIN CANNOT BE DIRECTLY CONNECTED TO SANITARY DRAINAGE SYSTEM