Permit: T09CM01965

Parcel: 13708021C


Addresses:

5601 S 12TH AV #07


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T09CM01965

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
11/19/2009 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
09/30/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) BOXES OVER FILLED-CK ON FINAL
2) OK WALLS AND LIDS
09/29/2009 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
There is no access to the site.| 920*
1) LOCKED, NO ACCESS
09/23/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK CEILINGS EXCEPT BATHROOMS 704, 705, 708 AND 709
2) OK PANEL 705
09/21/2009 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) USE APPROVED CONNECTORS WITH NM CABLES
2) SEPERATE GROUNDS AND NEUTRALS AT SUB PANELS
3) SECURE NM CABLES WITHIN 12" OF BOXES, CABINETS AND EQUIPMENT
08/31/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK 705-712 FIRE WALL ONLY
08/24/2009 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) MAINTAIN SEPERATION FOR FIRE STOPPING AND BACK TO BACK
2) SECURE SE CABLES WITHIN 8" OF SERVICE
3) PROTECT SE CABLE FROM SHARP METAL BOXES
4) SECURE CABLES ABOVE PANELS