Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/31/2009 | BUILDING - FINAL | Approved | IVRS - Inspection :* 1) PER INSTALLATION INSTRUCTION AND APPROVED PLAN ON SITE |
|
| 08/06/2009 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) PER WAND HEAT EXCHANGER SPECIFICATIONS SOLAR LOOP CONNECTION 15 3/8" COPPER WITH COMPRESSION FITTINGS, THESE FIXTURES ARE NOT TO BE SOLDERED 2) BRADFORD WHITE WATER HEATER HAVE A COMBINATION ANODE HOT WATER FITTING HAS THES BEEN REMOVED FOR THIS RETRO FIT ? PROVIDE A LISTING GIVING THE OK FOR THIS APPLICATION AND BRADFORD WHITES LISTING FOR THIS RETRO FIT 4) YOUR APPROVED PLAN DOES NOT INCLUDE AN INSTANT HOT PUMP. PLEASE PROVIDE APPROVED PLANS OF ACTUAL INSTALLATIONS, WITH CROSS OVER FITTING PROPERLY SUPPORTED 5) PIPING ON ROOF TO BE SUPPORTED AT CORRECT INTERVALS OFF OF ROOF ON WEATHER PROOF SUPPORTS 6) TERMINATE PANEL RELIEF VALVE TO AVOID 7) NOTE: CHANGES TO MANUFACTURERS LISTED DEVICES TYPICALLY VOID WARRENTYS |