Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/12/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 02/05/2010 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) STILL NEED AIR BALANCE REPORT PRIOR TO FINAL 2) ITEMS REQUIRED FOR DUCT SMOKE DETECTOR TEST ARE AS FOLLOWS: A) UNITS ARE TO BE TESTED WITH SMOKE UNLESS INSTALLATION INSTRUCTIONS SAY OTHERWISE, B) UNIT IS TO SHUT DOWN WITHIN 60 SECONDS OF ALARM, C) AUDIO AND VISIBLE ALARM ACTIVATES WHEN SMOKE IS DETECTED AND D) TEST IS PERFORMED BY THIRD PARTY (NOT MECHANICAL CONTRACTOR, OR FOR BALANCE COMPANY OR ALARM COMPANY |
|
| 02/04/2010 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* |