Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/30/2009 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 07/24/2009 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) VERIFY DUCT IN SOFFIT IN INSULATED WITH ALUMINUM R-4.2 2) FSK TAPE IS NOT APPROVED EXTERIOR APPLICATION 3) PROVIDE SECONDARY DRAIN ON A/C COIL 4) ALL PVC PIPING TO HAVE PRIMER AT ALL JOINTS PRIMER IS TO BE PURPLE IN COLOR PER UPC 5) PVC DRAIN IS TO TERMINATE 6' ABOVE GRADE 6) PROVIDE FILTER IN RETURN AIR STREAM |