Permit: T09CM01903

Parcel: 138142960


Addresses:

249 W HATFIELD ST

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
07/30/2009 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
07/24/2009 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) VERIFY DUCT IN SOFFIT IN INSULATED WITH ALUMINUM R-4.2
2) FSK TAPE IS NOT APPROVED EXTERIOR APPLICATION
3) PROVIDE SECONDARY DRAIN ON A/C COIL
4) ALL PVC PIPING TO HAVE PRIMER AT ALL JOINTS PRIMER IS TO BE PURPLE IN COLOR PER UPC
5) PVC DRAIN IS TO TERMINATE 6' ABOVE GRADE
6) PROVIDE FILTER IN RETURN AIR STREAM