Permit: T09CM01901

Parcel: 11618348C

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T09CM01901

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/21/2009 MECHANICAL - FINAL Approved IVRS - Inspection :*
12/18/2009 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) PROVIDE AIR BALANCE REPOR
2) PROVIDE ENGINEERS APPROVAL ON DAMPER LOCATION
3) WILL CHECK ROOF TOP CORRECTIONS ON NEXT VISIT
12/17/2009 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PERMANENTLY ID UNITS WITH SUITE NUMBERS OR ADDRESS
2) MARK UNIT DATA PLATE ON AC 2 AND FUSE ACCORDINGLY
3) CONNECT CONDENSATE DRAINS
4) CONNECT GAS PIPE TO A/C 1
5) SUPPORT ELECTRIC CONDUIT TO A/C 1
6) LOW VOLTAGE WIRE MUST BE PROTECTED USE CONDUIT A/C 1
7) A/C 1 OVERFUSED
8) AIR BALANCE WAIVED BY ENGINEER
9) EXTEND SEWER VENT MIN 2' ABOVE FRESH AIR INTAKE A/C2
10) TESTED DUCT SMOKE DETECTORS