Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T09CM01901
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/21/2009 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
12/18/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) PROVIDE AIR BALANCE REPOR 2) PROVIDE ENGINEERS APPROVAL ON DAMPER LOCATION 3) WILL CHECK ROOF TOP CORRECTIONS ON NEXT VISIT |
|
12/17/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PERMANENTLY ID UNITS WITH SUITE NUMBERS OR ADDRESS 2) MARK UNIT DATA PLATE ON AC 2 AND FUSE ACCORDINGLY 3) CONNECT CONDENSATE DRAINS 4) CONNECT GAS PIPE TO A/C 1 5) SUPPORT ELECTRIC CONDUIT TO A/C 1 6) LOW VOLTAGE WIRE MUST BE PROTECTED USE CONDUIT A/C 1 7) A/C 1 OVERFUSED 8) AIR BALANCE WAIVED BY ENGINEER 9) EXTEND SEWER VENT MIN 2' ABOVE FRESH AIR INTAKE A/C2 10) TESTED DUCT SMOKE DETECTORS |