Permit: T09CM01901

Parcel: 11618348C

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T09CM01901

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
12/21/2009 MECHANICAL - ABOVE CEILING Approved
11/20/2009 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO ONE ON SITE AT 10:00 AM
11/13/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) SEE NOTE 3 DATED 10/29/09
2) PROVIDE REGISTERS AND GRILLS PER PLANS OR PROVIDE WRITTEN APPROVAL FOR CHANGES FROM ENGINEER AND OR OWNER
3) ITEMS #1 & 2 DATED 10/29/09 COMPLETE
10/29/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) INSULATE ALL DUCT PER PLANS INCLUDING RETURN BOOT BOXES
2) PROVIDE SEISMIC RESTRAINTS ON ALL REGISTERS AND GRILLS IN T-BAR CEILINGS
3) PROVIDE VOLUMN DAMPERS AT ALL SUPPLY BRANCH TAPS