Permit: T09CM01901

Parcel: 11618348C

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T09CM01901

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
11/13/2009 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
10/29/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) MC TO BE SUPPORTED PER 330 NEC WITHIN 12" AND 6' INTERVALS, SUPPORT TO STRUCTURE NOT OTHER MC OR CONDUIT
2) INSULATE WHERE IN CONTACT WITH COPPER PIPING
3) REMOVE UNUSED CONDUITS AND CABLING