Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T09CM01901
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/13/2009 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
10/29/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) MC TO BE SUPPORTED PER 330 NEC WITHIN 12" AND 6' INTERVALS, SUPPORT TO STRUCTURE NOT OTHER MC OR CONDUIT 2) INSULATE WHERE IN CONTACT WITH COPPER PIPING 3) REMOVE UNUSED CONDUITS AND CABLING |