Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T09CM01847
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/20/2010 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* 1) DUCT IN MEZZANINE SOFFIT OK TO COVER |
|
09/28/2010 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) SUPPLY AND RETURN DUCTS IN SOFFIT ARE OK TO COVER, HOWEVER IT APPEARS THE RETURN AIR OPENINGS WILL BE BLOCKED BY DUCT WORK 2) PROVIDE AT ALL SIDE WALL AND CEILING BOXES BACKING 3) CONDENSATE DRAINS IN WALLS OK TO INSULATE AND COVER 4) BATHRROM EXHAUST MUST RUN CONTINOUSLY DURING OCUPPIED HOURS |
|
09/22/2010 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) SUPPLY AND RETURN IN DROP CEILING OK TO PROCEED |
|
08/18/2010 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) SUPPLY AND EXHAUST IN RESTROOMS OK 2) CONDENATE FROM PACKAGE UNITS OK |
|
07/21/2010 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) COMBUSTIBLES MATERIAL NOT ALLOWED IN A RETURN PLENIUM 2) SHEETROCK IN PLENIUM IS OK 3) DUCTING IN SOFFITS IN ? OK TO COVER |