Permit: T09CM01845

Parcel: 134113560


Addresses:

948 S SARNOFF DR

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
08/13/2009 MECHANICAL - FINAL Approved IVRS - Inspection :*
08/10/2009 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CORRECTION NOT MADE
2) SERVICE RECEPTACLE ON ROOF WAIVED
3) PAY A RE-INSPECTION FEE PRIOR TO NEXT INSPECTION
08/04/2009 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) PROVIDE A ROOF JACK AT CONDENSATE PENETRATION THRU ROOF
2) PROVIDE MINIMUM 1/8" PER FT SLOPE ON CONDENSATE DRAIN
3) PROVIDE THE REQUIRED GFI SERVICE RECEPTACLE ON ROOF
07/23/2009 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*