Permit: T09CM01845

Parcel: 134113560


Addresses:

948 S SARNOFF DR

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
08/13/2009 MECHANICAL - INTERMEDIATE Approved CORRECTIONS HAVE BEEN MADE
OK FOR FINAL
07/23/2009 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) YOU CANNOT USE BLACK WIRE FOR THE EQUIPMENT GROUND
2) PULL A NEW GREEN WIRE UP TO THE DISCONNECT
3) MARK THE UNIT DATA PLATE WITH PROPER HEAT STRIP
4) NEED TO VERIFY THAT 2" DUCT LINER WAS USED ON ROOF TOP DUCTING
5) TERMINATE CONDENSATE WITHIN 6" OF THE GROUND WITH AN ELBOW AND NIPPLE
6) RE-PAINT ALL PVC COMPLETELY WITH LATEX PAINT
7) TIGHTEN LOW VOLTAGE CONNECTION TO UNIT