Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/09/2009 | FRAMING | Approved | IVRS - Inspection :* | |
| 09/04/2009 | FRAMING | Not ready for Inspection | IVRS - Inspection :* 1) INSTALL GROUNDING CONDUCTOR #4 CU. FOR SERV. GRD. 2) RANGE CIRCUIT ON PLAN CALLS FOR #8 CU. 50/50 ROMEX CABLE IS RATED AT 40 AMPS ONLY 3) BANG PLATE ROMEX KIT. TOP PLATE 4) RANGE DUCT OUT OF WALL 5) BLK MECH MSTR CLOSET AREA 6) LEAVE H20 TEST ON DWV AND POTABLE H20 AFTER ALL ? REPAIRS |