Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UFER
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/21/2009 | ELECTRIC - UFER | Approved | IVRS - Inspection :* | |
| 08/17/2009 | ELECTRIC - UFER | Partial Approval | IVRS - Inspection :* 1) INSTALL MAIN BONDING SCREW |
|
| 08/13/2009 | ELECTRIC - UFER | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) COMPLETE ALL PREVIOUS ITEMS 2) TERMINATE PROPER LINE AND LOAD IN DISCONNECT 3) CHECK ALL TERMINALS TIGHT |
|
| 08/11/2009 | ELECTRIC - UFER | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) ONLY ONE CONDUCTOR PER ACORN LUG 2) MAINTAIN WORKING CLEARANCE AT SERVICE 110.26 3) BOND SERVICE NIPPLE AND USE APPROVED PARTS 4) WHAT VOLTAGE IS THIS SERVICE 5) USE APPROVED NEUTRAL KIT AT DISCONNECT 6) STRAP RISERS 7) FILL UNUSED OPENINGS AT SERVICE EQUIPMENT 8) ONLY ONE CONDUCTOR PER LUG AT TRANSFORMER 9) CANNOT USE ISOLATION STRAP FOR GROUNDING 10) PROTECT CONDUCTORS PER 352.46 AND 300.4 |
|
| 07/28/2009 | ELECTRIC - UFER | Partial Approval | IVRS - Inspection :* 1) NEED STRAPPING ON 1 1/2" PIPE BELOW PANEL FOR TRAILER #2 2) NEED K.O. SEAL BELOW PANEL FOR TRAILER #2 3) NEED STRAPPING ON 1 1/2" PIPE BELOW PANEL FOR TRAILER #1 |