Permit: T09CM01824

Parcel: 140430130

Inspection Status: Approved

Inspection History: ELECTRIC - UFER

Permit Number - T09CM01824

Inspection Description - ELECTRIC - UFER

Inspection Status - Approved

Date Description Inspector Results Comments
08/21/2009 ELECTRIC - UFER Approved IVRS - Inspection :*
08/17/2009 ELECTRIC - UFER Partial Approval IVRS - Inspection :*
1) INSTALL MAIN BONDING SCREW
08/13/2009 ELECTRIC - UFER Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) COMPLETE ALL PREVIOUS ITEMS
2) TERMINATE PROPER LINE AND LOAD IN DISCONNECT
3) CHECK ALL TERMINALS TIGHT
08/11/2009 ELECTRIC - UFER Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) ONLY ONE CONDUCTOR PER ACORN LUG
2) MAINTAIN WORKING CLEARANCE AT SERVICE 110.26
3) BOND SERVICE NIPPLE AND USE APPROVED PARTS
4) WHAT VOLTAGE IS THIS SERVICE
5) USE APPROVED NEUTRAL KIT AT DISCONNECT
6) STRAP RISERS
7) FILL UNUSED OPENINGS AT SERVICE EQUIPMENT
8) ONLY ONE CONDUCTOR PER LUG AT TRANSFORMER
9) CANNOT USE ISOLATION STRAP FOR GROUNDING
10) PROTECT CONDUCTORS PER 352.46 AND 300.4
07/28/2009 ELECTRIC - UFER Partial Approval IVRS - Inspection :*
1) NEED STRAPPING ON 1 1/2" PIPE BELOW PANEL FOR TRAILER #2
2) NEED K.O. SEAL BELOW PANEL FOR TRAILER #2
3) NEED STRAPPING ON 1 1/2" PIPE BELOW PANEL FOR TRAILER #1