Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/06/2010 | FIRE - FINAL | Approved | Approved 1/6/10. | |
| 10/02/2009 | FIRE - FINAL | Denied | 1.) Replace the ceiling tiles in the IT room. 2.) Portable fire extinguishers, required or non required, must be maintained and seviced or can be removed from service. 3.) Repair the panic hardware on the north double doors in room#110. 4.) Exit sign is burnt out in room #107. 5.) Replace all missing escusheons. 6.) Exit signs, exterior hall, ground floor are burnt out. 7.) Need a breaker blank, electrical panel. room # 105. 8.) Need a sign on the NW exterior gate that reads, "NOT AN EXIT" 9.) Can not direct towards a non exit door.(Exit sign next to room #106. 10.) The exit sign in room # 210 is burnt out. OK to operate kitchen. |
|
| 09/01/2009 | FIRE - FINAL | Partial Approval | OK to occupy offices. Not ready for restroom and kitchen. |