Permit: T09CM01819

Parcel: 13710512A


Addresses:

5660 S 12TH AV

Inspection Status: Approved

Inspection History: MECHANICAL - HOODS

Date Description Inspector Results Comments
09/28/2009 MECHANICAL - HOODS Approved
09/25/2009 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
1) SMOKE CONTAINMENT TEST-OK
2) HEAT SENSOR INTERLOCK COMES ON DID NOT SHUT DOWN 3) EXHAUST/MVA INTERLOCK OK
09/24/2009 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
1) HOOD EXHAUST AND MVA INTERLOCK OK
08/25/2009 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
1) REPAIR WRAP AT BACK OF DUCT, OK TO HANG HOOD-SECOND LAYER
08/24/2009 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
1) 1ST LAYER OF WRAP OK, OK FOR 2ND LAYER
08/21/2009 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
1) SMOKE TEST ON GREASE DUCT OK, OK FOR 1ST LAYER OF FIRE WRAP
2) OK FOR TILES ON SECOND FLOOR