Permit: T09CM01819

Parcel: 13710512A


Addresses:

5660 S 12TH AV

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
09/23/2009 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
09/10/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) CORRECT SHARED NEUTRAL PROBLEM ABOVE PANEL A-9
2) OK TO CLEAR A-9 SUBJECT TO POSTING OF BOND
08/26/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK ELECTRIC ABOVE CEILING 216-218
08/13/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) WALL PHONE PANEL OK
2) KITCHEN SOUTHWEST WALL OK
07/31/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) BUILDING INSPECTOR TO VERIFY FIRE STOPPING
2) NEED LETTER FROM ENGINEER FOR 1/2" CONDUIT. PLANS CALL FOR 3/4" MIN
3) OK WALLS ROOMS 117, 216-218 SUBJECT TO LETTER FROM ENGINEER
4) ABOVE CEILING 725.3 + 24, 800.3 + 24, 760.3 + 24 AND 300.11 WILL APPLY
5) 314.20 WILL APPLY ON WALLS
07/30/2009 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) OPEN WALLS TO SEE INSTALLED ELECTRIC
2) SUPPORT M/C CABLE AS PER 330.30