Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T09CM01819
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/23/2009 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 09/10/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) CORRECT SHARED NEUTRAL PROBLEM ABOVE PANEL A-9 2) OK TO CLEAR A-9 SUBJECT TO POSTING OF BOND |
|
| 08/26/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK ELECTRIC ABOVE CEILING 216-218 |
|
| 08/13/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) WALL PHONE PANEL OK 2) KITCHEN SOUTHWEST WALL OK |
|
| 07/31/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) BUILDING INSPECTOR TO VERIFY FIRE STOPPING 2) NEED LETTER FROM ENGINEER FOR 1/2" CONDUIT. PLANS CALL FOR 3/4" MIN 3) OK WALLS ROOMS 117, 216-218 SUBJECT TO LETTER FROM ENGINEER 4) ABOVE CEILING 725.3 + 24, 800.3 + 24, 760.3 + 24 AND 300.11 WILL APPLY 5) 314.20 WILL APPLY ON WALLS |
|
| 07/30/2009 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) OPEN WALLS TO SEE INSTALLED ELECTRIC 2) SUPPORT M/C CABLE AS PER 330.30 |