Permit: T09CM01776

Parcel: 137055240

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T09CM01776

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
09/04/2009 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
08/06/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) PROVIDE OSD'S PER PLANS
2) PROVIDE ENGINEERS APPROVAL ON FLEX DUCT IN EXCESS OF 6'
3) PROVIDE ENGINEERS APPROVAL ON FLEX DUCT WORN CLAMPS TO BE SUBSTITUTED WITH PLASTIC DRAW BANDS
4) SUPPORT FLEX DUCT OFF OF COPPER PIPE
5) OK FOR TILES WITH APPROVAL OF ITME 1,2 & 3