Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T09CM01776
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/08/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) OK ELECTRIC |
|
09/03/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) ALL DENTAL EQUIPMENT TO BE LISTED AND LABELED 2) PUMP AND VACUUM NOT CORD, PLUG EQUIPMENT-M/C NOT FOR USE WITH PLUG ATTACHMENTS 3) LIGHT NOT PER 700.12 (F) |
|
08/28/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) NEED TO SEE DENTAL EQUIPMENT 2) EM LIGHTING FOR LIFE SAFETY TO BE AS PER 700.12 (F) |