Permit: T09CM01776

Parcel: 137055240

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/08/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
1) OK ELECTRIC
09/03/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) ALL DENTAL EQUIPMENT TO BE LISTED AND LABELED
2) PUMP AND VACUUM NOT CORD, PLUG EQUIPMENT-M/C NOT FOR USE WITH PLUG ATTACHMENTS
3) LIGHT NOT PER 700.12 (F)
08/28/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) NEED TO SEE DENTAL EQUIPMENT
2) EM LIGHTING FOR LIFE SAFETY TO BE AS PER 700.12 (F)