Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/08/2009 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 08/21/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 08/20/2009 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* OK ELECTRIC ABOVE CEILING |
|
| 08/18/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) SUPPORT M/C CABLE WITHIN 12" OF CANS AND BOXES 2) VERIFY BOX FILL 3) VERIFY DERATING AT PANEL-10 CONDUCTORS IN RACEWAY 310.15 (2 RACEWAY) 4) OK HARD LID AFTER CORRECTIONS TO CAN AND BOX |