Permit: T09CM01776

Parcel: 137055240

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
09/08/2009 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
08/21/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
08/20/2009 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
OK ELECTRIC ABOVE CEILING
08/18/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) SUPPORT M/C CABLE WITHIN 12" OF CANS AND BOXES
2) VERIFY BOX FILL
3) VERIFY DERATING AT PANEL-10 CONDUCTORS IN RACEWAY 310.15 (2 RACEWAY)
4) OK HARD LID AFTER CORRECTIONS TO CAN AND BOX