Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/06/2009 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* 1) OK TO COVER ALL AREAS 2) GAS PRESSURE TEST OK |
|
| 10/05/2009 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) 1 1/2" TRAP ARM MAY ONLY EXTEND 36" FROM POINT OF VENT TO TRAP WEIR 2) TRAP ARM MAY ONLY CHANGE DIRECTION 90 DEGREE WITHOUT ADDITIONAL CLEANOUT 3) HOT WATER INSULATION TO COMPLY WITH 2006 I.E.C.C. 4) HORIZONTAL X HORIZONTAL CHANGE OF DIRECTION TO BE A SWEEP 5) NEED TO SEE CLOSET FLANGE 6) NAIL GUARDS 7) FHA STRAPS |