Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T09CM01703
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/24/2009 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
08/20/2009 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. SUPPORT M/C CABLE PER 300.11 2. USE APPROVED METHOD TO SUPPORT VDV CABLING CANNOT LAY ON PIPE OR USE TIE WIRE OR THHN 725.24, 800.24, 300.11, 110.3 |
|
08/13/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) PROPERLY SUPPORT TELEPHONE AND DATA CABLES- MINIMUM EVERY 6' 2) WILL CHECK POWER POLES AT FINAL 3) ENSURE JUNCTION BOXES GET BLANKED |