Permit: T09CM01703

Parcel: 13414001K

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T09CM01703

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
08/24/2009 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
08/20/2009 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. SUPPORT M/C CABLE PER 300.11
2. USE APPROVED METHOD TO SUPPORT VDV CABLING
CANNOT LAY ON PIPE OR USE TIE WIRE OR THHN

725.24, 800.24, 300.11, 110.3
08/13/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) PROPERLY SUPPORT TELEPHONE AND DATA CABLES- MINIMUM EVERY 6'
2) WILL CHECK POWER POLES AT FINAL
3) ENSURE JUNCTION BOXES GET BLANKED