Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T09CM01698
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/21/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1) DUCT SMOKE DETECTOR TEST OK 2) AIR BALANCE OK 3) OK FOR FINAL |
|
04/20/2010 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
04/16/2010 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) PERMANENTLY I.D. EQUIPMENT ON ROOF 2) PROVIDE A PROTECTIVE COATING ON EXPOSED ARAMFLEX 3) DO NOT REDUCE CONDENSATE FROM SIZE OF OUTLET ON A/C UNIT 4) 7 1/2 TON UNIT CONDENSATE TRAP BACKWARDS AND BACK SLOPE ON DRAIN LINE 5) PROVIDE AIR BALANCE REPORT 6) NEED TO TEST DUCT SMOKE DETECTOR |