Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T09CM01698
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/23/2010 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
04/21/2010 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) SOLAR PANELS TO BE PROPERLY SUPPORTED, ORIENTED AND SECURED 2) COMPLETE ITEMS 2 WITH CERTIFICATION 3) COMPLETE ITEMS 5 & 6 4) COMPLETE ITEMS #8 5) COMPLETE INSULATION ON HOT PIPING 6) STERILIZATION AND BACTERIA REPORT ON SITE |
|
04/20/2010 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) CONTRACTOR CANCELLED |
|
04/19/2010 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) PROVIDE TERMINATION OF EXTERIOR SEWER CLEANOUT DOWN STREAM OF INTERCEPTOR 2) PROVIDE RPB AT WATER FILL STATION AT AIR/WATER DISPENSER 3) SEAL ROOF JACK WEATHER TIGHT FOR SOLAR PENETRATIONS 4) PROVIDE PETITION OF APPEAL FROM BLDG OFFICIAL FOR WATERLESS URINAL USE 5) SUPPORT SOLAR PANELS TO ROOF SUPPORTS PER MANUFACTURES INSTALL INSTRUCTIONS 6) SUPPORT SOLAR ROOF TOP SUPPORTS TO BLDG STRUCTURE 7) INSTALL WATER HEATER PER DETAIL #9 8) FLOOR SINKS REQUIRE STRAINERS AND GRATES 9) SECURE ACCESS PANELS TO WALLS 10) PROVIDE CORRECT DRAINAGE FITTINGS, APPROVED HANGERS AND CORRECT FAU ON ALL INDIRECT PIPING 11) LIST NOT COMPLETE |