Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - SEWER HCS CONNECT
Permit Number - T09CM01698
Inspection Description - PLUMBING - SEWER HCS CONNECT
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/01/2009 | PLUMBING - SEWER HCS CONNECT | Approved | IVRS - Inspection :* | |
11/25/2009 | PLUMBING - SEWER HCS CONNECT | Not ready for Inspection | IVRS - Inspection :* 1) PROVIDE APPROVED PRIMER AND GLUE FOR PVC TO PVC CONNECTION AT STD BUSHING 2) TEST INLET PIPING TO INTERCEPTOR, FROM INTERCEPTOR THRU DAMPLING PORT AND 2 WAY CLEANOUT WATER TEST OK 3) MAKE APPROVED TIE IN FROM 2-WAY AT SAMPLING PORT TO SEWER 4) SAMPLING PORT TO BE BUILT ON BASE LIKE FLOW BENCH FOR MANHOLE |
|
11/23/2009 | PLUMBING - SEWER HCS CONNECT | Partial Approval | IVRS - Inspection :* 1) 4" SITE SEWER FROM EXISTING 6" PROPERTY STUB, UPSTREAM TO 5' FROM GREASE INTERCEPTORS, 4" SEWER WYES TO (2) 4" BLDG SANITARY DRAINAGE CONNECTIONS, ALL TO BE INSPECTED AT LATER DATE 2) WATER TEST OK PER INITIAL ON PLAN 3) 4" GREASE WASTE NEEDS INSPECTION FROM 5' EXTERIOR INTO INTERCEPTOR |